    您當前的位置:首頁 > 技術文章 > Common faults and causes of zirconia oxygen analyzers

    Common faults and causes of zirconia oxygen analyzers

    發布時間: 2024-12-13  點擊次數: 260次

    1. System maintenance.

    If the oxygen indicator shows zero or no oxygen indication in the oxygen quantity converter, first check whether the oxygen indication circuit open. If the circuit is normal, check whether the zirconia probe is normal. At a temperature of 700℃, measure the DC millolt value of the oxygen cell. If the potential is greater than 1 millivolt and the resistance is greater than 100Ω, it indicates the probe is aged and needs to be replaced with a sensor or probe. If the potential is less than 1 millivolt and the resistance is less than100Ω, it indicates an open circuit in the wiring, which should be checked and handled one by one.

    2. constant temperature system failure.

    (1) If the heating temperature cannot be maintained, check whether there is a short circuit or open circuit in the resistance wire inside the heating furnace The normal resistance of the heating furnace wire is about 60-80Ω. If the resistance wire is open or the resistance measured by the multimeter less than 60Ω, the heating furnace wire should be replaced.

    (2) When the converter shows that the temperature is too high or out of control, it not only causes inaccurate oxygen display but also acceler the aging or damage of the zirconia head. At this point, you should immediately check if the thermocouple is open-circuited, or a multimeter to check the thermocouple. If the resistance is greater than 20Ω, it is judged that the thermocouple is open-cuited, and the thermocouple and zirconia head should be replaced; another reason for the temperature失控is: relay or temperature control circuit failure, relay or temperature control circuit failure will cause the oxygen converter to always be in one of the heating voltages of the heating furnace, thus leading to an increase in.

    3. oxygen cell fault.

    (1) After the oxygen cell has been used for a period of time, the contact points of its leads may become oxidized, resulting in contact or detachment. This can cause the Em value (in units of a multimeter) to fluctuate and become unstable. Observe the oxygen cell and take action.

    (2) When the oxygen signal deviation is too large or inaccurate, it may be due to a short circuit in the zirconia electrode, which case the wiring of the zirconia cell should be checked for short circuits. When the temperature does not rise, if the internal resistance is less than 0Ω, it indicates a short circuit in the electrode, and the zirconia head needs to be replaced.

    (3) During the operation of the oxygen measurement device, if the background potential exceeds 10mV or is less than -30mV, it must be recalibrated. If the background potential remains abnormal after calibration, it indicates that the probe has aged and can no longer be used.

    4. pneumatic circuit failure.

    (1) The zirconia head is clogged with ash, causing an obstruction in the reference gas circulation. This results in a decrease in probe output potential Em and an increase in the background potential Eo. In this case, blowing several times with a bulb syringe at the gas inlet of the will resolve the issue after the gas line is unclogged.

    (2) Oxygen cell ash blockage: The probe should be removed from the ash blockage and the filter should be reinstalled.

    (3) Probe leakage has a significant impact on the probe.

    5. The oxygen content on both sides of the boiler is too high.

    By adjusting the boiler combustion conditions, when starting or stopping the boiler fan or coal mill group, if the oxygen content deviation on both sides of the boiler is large, it is a normal phenomenon. Once the boiler combustion conditions stabilize, the oxygen content display will return to normal. If the unit adjustment is not in place and the deviation is large on both sides, it is necessary to check if the zirconia head is working properly by dismantling the transmitter for inspection. The device requires the operator to adjust the gas flow. The gaseous and reference state gases should continuously flow through the electrode without stopping, and there should be no dead ends. However, too large a flow will have a cooling effect, making the cell temperature uneven and causing errors. If the flow is too small, it is not only easy to form stagnant gas flow and dead zones but also may cause local changes in oxygen concentration due to the conduction of oxygen ions, thus affecting the accuracy of the measurement and causing deviations on both sides.

    6. On-site interference causes failures.

    For newly installed instruments, due to the strong electromagnetic field, when an unstable fault occurs, the first thing to consider is the interference issue.


在線客服 聯系方式 二維碼

服務熱線

0550-2409223

掃一掃,關注我們

皖公網安備 34118102000850號

主站蜘蛛池模板: 在线观看h片 | 亚洲va久久久久 | 一级做a爱片特黄在线观看免费看 | 特级黄毛片 | 超级碰碰青草久热国产 | 妹子草网| 中文国产成人精品久久一区 | 国产美女网址 | 亚洲国产精品日韩在线观看 | 成人在线视频网址 | 成人免费看片网站 | 国产女人精品性视频 | 香蕉97| 免费一区二区视频 | 欧美中文字幕 | 午夜精品一区二区三区在线视 | 人体大胆做受免费视频 | 三级黄色大片 | 99久久99久久精品免费看蜜桃 | 麻豆激情| 日鲁夜鲁天天鲁视频 | 亚洲精品无线乱码一区 | 国产在线高清一级毛片 | 皇色在线视频 | 亚洲一区免费观看 | 亚洲高速浪潮 | xxx日本免费 | 国产一二区视频 | 国产精品小黄鸭一区二区三区 | 国产精品一国产精品 | 草草视频在线 | 日本黄色绿像 | 国产成人在线视频免费观看 | 久久国产亚洲高清观看5388 | 精品综合 | 久久久久99精品成人片三人毛片 | 日韩区欧美区 | 精品外国呦系列在线观看 | 国产精品国产欧美综合一区 | 精品成人免费一区二区在线播放 | 国产免费私拍一区二区三区 |